Basic Info.

Model NO.
SS1503
Operation Condition
Indoor
Usage
Measurement
Winding Form
Single Layer & Tightly Wound Type
Insulating Medium
Epoxy Resin
Installation
Busbar Type
Magnetic Circuit Structure
Combined Type
Voltage Transformation Principle
Electromagnetic Type
Transport Package
Carton
Specification
38.5*22*22cm
Trademark
Bingzi
Origin
China
HS Code
8504311000
Production Capacity
10000000per Year

Product Description

SS1503 Series Rectangular AC Current Transformer
LI130V2 /2016

1.Features:
Directly fixed on the 17 × 4 flat busbar ;
 Fully enclosed, good mechanical and environmental resistance, strong voltage isolation capability, safe and reliable .

2.Ambient Conditions:
Ambient temperature: -55ºC~+85ºC;
Relative humidity: ≤90% at 40ºC;
Atmospheric pressure: 860~1060mbar(about 650~800mmHg).

4.Insulation Thermal Class:Class B ( 130 ºC )

5.Safety Features:
Insulation resistance: >1000MΩ in normal condition;
Insulation withstand voltages: 6KV 50Hz/1min;
Fire retardancy: In conformity with UL94-V0.

6. Outline Drawing, Installation Dimension and Coil Diagram: (tolerance ± 0.5mm)
Outline drawing and installation dimensions are shown in Figure 1 :

SS1503 Series Rectangular AC Current Transformer
The coil diagram is shown in Figure 2 :
SS1503 Series Rectangular AC Current Transformer
7. Performance Parameters:
See the table below for the application performance parameters shown in Figure 3.
SS1503 Series Rectangular AC Current Transformer

3.Operating Frequency Range: 20Hz~1k Hz

Model Rated
Input Current
Rated
Output Current
Rated
Sampling Resistance
Rated
Sampling Voltage
Phase Shift Non-linearity Linear Range
SS1503-01 15A 0.1A 0.6V ≤30' ≤0.5% ≥ 2 times of the rated value
SS1503-02 20A 0.8V ≤30' ≤0.5%
SS1503-03 25A 10Ω 1.0V ≤30' ≤0.5%
SS1503-04 35A 14Ω 1.4V ≤30' ≤0.5%
SS1503-05 40A 16Ω 1.6V ≤30' ≤0.5%
SS1503-06 50A 20Ω 2.0V ≤30' ≤0.5%
SS1503-07 65A 26Ω 2.6V ≤30' ≤0.5%
SS1503-08 75A 30Ω 3.0V ≤30' ≤0.5%

Notes:
a. In practical applications, the sampling resistance should be less than or equal to the Rated value given in the above table, which will improve the nonlinearity and Phase Shift;
b. If the conversion ratio required by the user is different from the above, it can be customized according to the user's requirements.

8.Attention:
 The primary winding of the current transformer should be connected in series with the current circuit under test. The secondary winding should be operated close to a short-circuit condition.
 The secondary circuit of the current transformer must not be open-circuited. Therefore, do not install a fuse in the secondary circuit.
 